10HIGH ALTITUDE Inputs are derated 4% for each 1000 ft (305m) elevation above 2000 ft (610m). INDOOR UNITS Install an indoor unit such that the
11CAUTION-GAS UNITS • At maximum input the supply gas pressure must fall within the range specified on the unit rating plate. • Check all piping
12 1. RECOMMENDED OUARTERLY MAINTENANCE a) Check for loose connections in the wiring. b) Check the voltage at the unit while it is in operation
13MARKINGS FOR YOUR SAFETY If you smell gas: 1. Open Windows. 2. Don't touch electric
14 FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and
2Table of Contents Receiving and Warehousing 3 General Handling instructions 3 General Installation Notes
3RECEIVING AND WAREHOUSING Inspect the unit upon arrival for any shipping damage. If any part is missing or damaged, mark the bill of lading as to d
4c) No alterations are to be made on this equipment. d) For suspended appliances that are installed in aircraft hangers, parking structures, and re
5CONNECTING THE FLUE (VENTING) OUTDOORS INSTALLATIONS AIR FOR COMBUSTION Openings for combustion air must be provided in a panel (door) with dir
61. Air from inside the building – Opening of 1 square inch (sq. n.) per 1000 Btuh of input, but never less than 100 sq. in. 2. Air from outside (d
7 All vent pipe joints must be sealed to prevent leakage into the heated space. Follow instructions provided with approved venting material used. T
8heated space and vent products of combustion outdoors. No air openings are to be provided in the vestibule access door or panel and sealing grommet
9 GAS PIPING All gas piping should be in accordance with National Fuel Gas Code ANSI Z223.1, and CAN 1-B149 with the regulation of local authoritie